Why Sizing Backup Hours Matters
Our system tiers guide gave broad recommendations for light, moderate, and severe outage areas. This final post in the load-shedding series gives you the actual math — so you can validate (or adjust) a recommended tier against your specific household load and real outage pattern, instead of trusting a generic estimate.
This matters because an undersized battery leaves you without power halfway through a cut — the exact failure mode a backup system is supposed to prevent — while an oversized battery wastes capital that could have gone toward more panels or a larger inverter.
Want our team to run this calculation for your specific home? Ask on WhatsApp.
The Backup Sizing Formula
Step 1 — Audit Your Essential Load
Essential load is what you actually want to keep running during an outage — not every device in your house. Focus on items you can't easily do without for several hours.
| Device | Typical Running Load |
|---|---|
| Ceiling fan | 60–75 W |
| LED bulb | 8–12 W |
| WiFi router | 10–15 W |
| Refrigerator (avg. cycling) | 150–250 W |
| LED TV | 60–100 W |
| Laptop charger | 60–90 W |
| Water pump (1 HP) | 750 W (brief, high-demand) |
| 1-ton inverter AC | 900–1,200 W continuous |
| 1.5-ton inverter AC | 1,400–1,800 W continuous |
Add up what you actually need running simultaneously during a typical outage — that's your essential load number in kW (watts ÷ 1000).
Step 2 — Estimate Your Worst-Case Outage Hours
Our Punjab schedule guide covered seasonal and regional variation. For sizing purposes, use your worst-case single-outage duration, not an average — a system sized to the average will fail during the worst cuts, which is exactly when you need it most.
- Light exposure (central urban areas): Plan for 2-3 hour worst-case single outages
- Moderate exposure (outer housing schemes): Plan for 4-6 hour worst-case single outages
- Severe exposure (high-loss feeders, industrial-adjacent zones): Plan for 6-10 hour worst-case single outages
Step 3 — Apply the Safety Margin
The 1.3× safety margin accounts for three real-world factors that shrink usable battery capacity below its nameplate rating:
- Depth of discharge limits — lithium batteries shouldn't be drained to 0% regularly, leaving some capacity off-limits for long-term health
- Inverter conversion losses — around 3-5% of stored DC energy is lost converting to AC for your appliances
- Battery aging — a battery that's 5 years old delivers slightly less than its day-one capacity
Multiplying your raw requirement by 1.3 covers these losses for most residential scenarios.
Worked Examples
| Scenario | Essential Load | Worst-Case Hours | Battery Needed |
|---|---|---|---|
| Studio apartment — fans, lights, router, laptop | ~0.3 kW | 4 hours | ~2 kWh |
| Small household — fans, lights, fridge, router, TV | ~0.6 kW | 6 hours | ~5 kWh |
| Standard Lahore household — + water pump occasional | ~1.0 kW | 6 hours | ~8 kWh |
| Household + 1 AC running during outage | ~2.2 kW | 6 hours | ~18 kWh |
| Severe-exposure home + 2 ACs for whole family | ~3.5 kW | 8 hours | ~36 kWh |
Run the formula with your real essential load and your real worst-case outage duration before committing to a battery size — don't trust a round-number estimate alone. Most homes undersizing their backup do so because they skipped the AC load calculation or used an "average" outage duration instead of worst-case. Err on the side of one battery size up when the numbers are borderline.
Share your bill and essential loads and we'll run the full backup sizing for you. Get a free sizing consultation on WhatsApp →
Battery Options by Calculated Size
5 kWh Battery Bank
Covers small households with modest essential load and light-to-moderate outage exposure.
View 5 kWh options →10 kWh Battery Bank
The sweet spot for standard Lahore households facing moderate outage patterns.
View 10 kWh options →20 kWh+ Stacked Bank
Needed when AC coverage during outages is a must or severe-tier exposure applies.
View battery guide →Frequently Asked Questions
Repeatedly deep-discharging a lithium battery below ~20% remaining shortens its cycle life significantly — the 1.3 safety margin ensures normal use stays within healthy depth-of-discharge limits.
Nighttime — during the day, solar panels recharge the battery continuously, so the battery is primarily tested during evening and overnight outages when solar isn't contributing.
More panels increase daytime generation and recharge speed but don't directly change the battery capacity needed for nighttime outage coverage — the two sizing decisions are related but independent.
Only if your inverter supports battery expansion and your battery model allows adding matching stacked units — otherwise, retrofitting a mixed battery bank later can cause BMS compatibility issues.
Inverter ACs are more efficient than fixed-speed units, but any AC — inverter or not — represents a substantial load compared to fans and lights, which is why AC coverage significantly changes your sizing calculation.
Check each appliance's label (usually shows wattage), use the typical values in the table above as estimates, or ask your installer to do a quick load audit during the site survey.